Read-only live values from a running TIA Portal V21, for AI agents. An MCP server (stdio) that lets an agent check the online state of a PLC, read the actual values of data blocks and look at a monitored watch table, tag table or block - without someone taking screenshots by hand.
It is one of the four tools of the BetterTIA set:
| Tool | Role |
|---|---|
| reader | reads a TIA Portal project through Openness and exports it to a folder (read-only MCP server) |
| writer | writes to a TIA Portal project through Openness (MCP server) |
| editor | draws a network from the export, lets you compose a change and tracks it until it is in the project |
| watch (this repository) | reads live values from the running PLC through TIA Portal (read-only MCP server) |
All four are developed, used and tested only with TIA Portal V21.
Status: early (0.1.x). The tools are tested against a fake TIA Portal and were checked once against a real PLC with TIA Portal V21 (see below); what only the fake covers is marked there.
| Tool | What it does | Source |
|---|---|---|
watch_online |
Online state of a PLC (OnlineProvider.State); action goOnline connects to an allowed target address over a named pcInterface (or adopts a connection that is already online), goOffline disconnects |
Openness |
watch_db |
Actual values of one or more data blocks: ValueService.CreateSnapshot(), then InterfaceSnapshot.Export() with read-only attributes; returns the snapshot time and one path = value (type) line per member (section headers left out; at most maxRows rows per block, default 500, otherwise truncated: true and the number of rows left out; the answer ends with projectMarkedModified). Technology objects (PID_Temp, PID_Compact, ...) are found by name, but Openness V21 gives no actual values for them (Interface is not supported on TechnologicalInstanceDB): the call says so and points to a watch table with watch_screen; members keeps only the members at or below the given paths (e.g. State,Config.Input). Requires the PLC to be online |
Openness |
watch_screen |
Opens a watch table, tag table or block (ShowInEditor()), switches monitoring on when allowed (Monitor button through MSAA, Ctrl+T "Monitor all" as fallback), and returns a PNG capture of the TIA Portal window (PrintWindow) as MCP image content |
Openness + Win32 |
Common parameters: plc (PLC software name, optional when the project has one PLC) and portalId (process id,
optional when one TIA Portal is running). The server attaches to a running TIA Portal; it never starts one.
| Environment variable | Meaning |
|---|---|
BTIA_WATCH_ALLOWED_TARGETS |
Comma-separated IP addresses watch_online goOnline may connect to, e.g. 192.0.2.10,192.0.2.11. Empty or unset: goOnline is refused and the tool only reports the state. |
- Going online only to an allowed address.
goOnlinecallsOnlineProvider.GoOnline(ConfigurationAddress)with the given target on the given PG/PC interface (ConnectionConfiguration.Modes->PcInterfaces->Addresses). The parameterlessGoOnline(), which connects over the last used interface to the address stored in the project, is never called; a test scans the sources for it. - Monitor button first, Ctrl+T only as fallback. Monitoring is switched on by pressing the editor's "Monitor"
toolbar button through MSAA (
accDoDefaultAction): TIA Portal is not brought to the front and no keys are sent. Ctrl+T is sent only when no button could be pressed or monitoring still reads as off after the press (not when the state is unreadable after a press: Ctrl+T toggles). The result says which path was used. Not yet checked against TIA Portal. - Ctrl+T only over a connection this server opened or adopted. In an offline editor Ctrl+T makes TIA Portal open its
"Go online" dialog and connect by itself over the last used interface.
watch_screentherefore sends Ctrl+T only whenOnlineProvider.StateisOnlineand the connection was opened bywatch_online goOnlineof this server process (an adopted connection counts, see below). Otherwise it captures the editor without the shortcut and says why. The Monitor button is kept to the same rule.sendShortcut=falsepresses and sends nothing. - Ctrl+T is a toggle. Before sending it, the server reads the pressed state of the editor's "Monitor" toolbar button (MSAA) and sends Ctrl+T only when monitoring is off; afterwards it reads the state again. When the button cannot be read, Ctrl+T is sent once with a warning. One call sends it at most once.
- Adopted connections. If the PLC is already online (for example from an earlier server process),
goOnlinestill checkstargetagainst the allowed list and then adopts the connection. Openness does not expose the address of an open connection, so the adopted connection is not compared withtarget. - Foreign dialogs. If a new window of the TIA Portal process appears after the button press or Ctrl+T, it is closed with Esc and the call fails.
- Focus. A minimized TIA Portal window is restored without activation before the capture; only for the Ctrl+T fallback TIA Portal is brought to the front (no Alt key: it opens the menu bar) and the previous foreground window gets the focus back after the capture. Keys are only sent when TIA Portal really is the foreground window.
- No empty snapshots.
CreateSnapshot()offline returns without error and leaves the snapshot empty, sowatch_dbrefuses to run unless the PLC is online.
- Nothing writes values to the PLC. The value-loading methods of
ValueServiceare not called anywhere in the code, and no parameter can reach them. A test scans the sources for them. - Fail-safe data blocks are refused by
watch_db(tested only against the fake: the refusal sits in the Openness layer, which the tests do not reach). - Side effects that remain:
watch_dbstores the snapshot in the offline project, so TIA Portal shows the project as changed (the server never saves it, and Openness has no way to undo it; the answer reportsprojectMarkedModified);goOnlinecreates the given address on the PG/PC interface when it is not there yet, which also changes the offline project;watch_screenopens an editor and, only on the Ctrl+T fallback, briefly brings TIA Portal to the front.
Checked against TIA Portal V21 with a real PLC: goOnline over a named PG/PC interface, adopting an existing
connection, watch_db values of global DBs with structures and arrays, watch_screen on a watch table, a tag table
and a LAD block (monitoring state read, Ctrl+T sent only when off), goOffline. Call the tools one after another:
two concurrent watch_screen calls fight over the active editor.
Not yet checked: instance DBs of GRAPH blocks, very large DBs (the maxRows cut is tested only against the fake),
projectMarkedModified (reads Project.IsModified; fake only), floating editors (found by window title; fake only),
other monitors and DPI scaling.
- Windows, .NET Framework 4.8
- Siemens TIA Portal V21 with Openness, running with a project open
- The user is a member of the Windows group
Siemens TIA Openness - User environment variable
TiaPortalLocationpointing to the TIA Portal V21 installation folder
dotnet build BtiaWatch.slnx -c Release
dotnet test BtiaWatch.slnx -c Release
The tests need neither TIA Portal nor a PLC: the tools run against a fake IWatchPortal, and the window capture is
tested on a window of the test process.
A running server locks its .exe, so build a copy per version and point the client at that copy, e.g.
dotnet build src\BtiaWatch -c Release -o dist\0.1.5 (dist/ is ignored by git). Add the server to .mcp.json
under the key BTIA_Watch:
"BTIA_Watch": { "type": "stdio", "command": "<repository>\\dist\\0.1.5\\BtiaWatch.exe", "args": [], "env": { "BTIA_WATCH_ALLOWED_TARGETS": "192.0.2.10" } }
MIT, see LICENSE.