Industrial digital I/O slice for BREAD: four 12–24 V inputs and four solid-state relay outputs, for sensors and actuators on a 24 V field supply.
An Arduino Nano on the 10-pin slice bus (G3, Slice Interface 1), 70 × 100 mm, two layers. Hardware revision r2.
The slice works like a small PLC I/O module. Each input reads a field signal through an optocoupler with a switching threshold; each output is a photo-MOSFET relay that switches a load from the field supply or acts as a dry contact. A low level on the bus e-stop line turns every output off in hardware, whatever the firmware does.
Each input has three terminals: INx+, INx- and GND.
- Floating (isolated): connect the sensor's output between
INx+andINx-. The source must provide its own return path. - Board-referenced: link
INx-to theGNDterminal beside it and driveINx+against board ground.
An input reads OFF below about 7 V and ON from 11 V; it is rated to 30 V. A reversed input does no harm. The Nano reads IN1–IN4 on D9, D8, D7 and D6, high when the input is on.
Each output has three terminals: OUTx-, OUTx+ and VF (VFIELD).
- Wet contact: link
VFtoOUTx+(the next terminal) and wire the load fromOUTx-toGNDon J1. - Dry contact: leave
VFunconnected and useOUTx+/OUTx-as a DC switch,OUTx+the more positive, up to 30 V.
Each output is rated 0.7 A and has a unidirectional TVS diode across it (33 V standoff), which is why the outputs switch DC only. Fit a flyback diode across an inductive load anyway. The Nano drives OUT1–OUT4 on A0–A3, high to switch on.
| J1 pin | Use |
|---|---|
| 1 | +24 V field supply in |
| 2 | 0 V of the field supply |
| 3, 4 | GND, return for wet-contact loads |
The 24 V input has reverse-polarity protection and a 30 V TVS diode. JP1 picks where VFIELD comes from:
| JP1 shunt | VFIELD |
|---|---|
| 1–2 | the external supply on J1 |
| 2–3 | the bus +12 V |
VFIELD is limited to 2 A in total. Taking it from the bus loads the backplane's 12 V supply.
Bus pin 6 is the e-stop line (5 V = run, low = stop). It gates the relay drive through Q2, so a stop, or a slice pulled from the bus, turns all four outputs off. The Nano reads the same line on D2.
See docs, including the r2 revision plan.