GeezerVison is showing github.com — GitHub - jamesccupps/PPCL: PPCL Workbench: IDE, linter, simulator and debugger for Siemens PPCL (APOGEE/PXC). 90 lint rules, each cited to the manual. Python stdlib, runs locally.

BranchesTags
Open more actions menu

Latest commit

 

History

167 Commits
167 Commits

Folders and files

NameName
Last commit message
Last commit date
.claude-plugin
.claude-plugin
 
 
.claude
.claude
 
 
.github/workflows
.github/workflows
 
 
commands
commands
 
 
diagrams
diagrams
 
 
docs
docs
 
 
panel-tests
panel-tests
 
 
ppcl
ppcl
 
 
samples
samples
 
 
sequences
sequences
 
 
skills/ppcl
skills/ppcl
 
 
tests
tests
 
 
.gitattributes
.gitattributes
 
 
.gitignore
.gitignore
 
 
.mcp.json
.mcp.json
 
 
CLAUDE.md
CLAUDE.md
 
 
LICENSE
LICENSE
 
 
PLUGIN.md
PLUGIN.md
 
 
README.md
README.md
 
 
SECURITY.md
SECURITY.md
 
 
__main__.py
__main__.py
 
 
ppcl.bat
ppcl.bat
 
 
ppcl_mcp.py
ppcl_mcp.py
 
 
pyproject.toml
pyproject.toml
 
 

Repository files navigation

PPCL Workbench

tests Latest release License: MIT

Website: jamesccupps.github.io/PPCL · Download the latest release

Read, inspect, lint, debug, optimize and write Siemens PPCL.

PPCL is not a legacy language. Siemens' 2025 reference manual for its current panels points you at the same PPCL User's Manual (125-1896) that covered the old ones, and its 2026 modernization guide converts PPCL onto the new hardware rather than off it. You edit it in Desigo — on the panel itself if you have to, but that is not where the work happens. This toolkit covers six firmware families.

Zero dependencies, Python 3.10+, stdlib only. Everything runs locally — no program text ever leaves the machine.

The Editor with a sample program open: syntax coloring, two warnings marked in the gutter, and the findings below, each with its fix and the manual chapter it comes from

The Bench after a three-hour design-winter run with a stuck outdoor-air damper injected at 30 minutes: the notes on what was simulated and what priority blocked, the trends, and the checks that failed and passed

The samples that ship in samples/ and sequences/, in the browser workbench (python -m ppcl serve).

Running it

Nothing to install.

On Windows, double-click ppcl.bat. It finds a suitable Python, starts the workbench and opens it in your browser. The same file takes a subcommand if you would rather use the command line — ppcl.bat lint programs\ — and passes the exit code through, so it drops into a build script unchanged.

Otherwise, stand in the directory and run:

python -m ppcl serve

That opens the workbench in a browser. For the command line, the same module takes a subcommand:

python -m ppcl lint  path/to/programs/
python -m ppcl bench AHU1.ppcl --weather design_winter
python -m ppcl bench AHU1.ppcl --fault "AHU1,oa_damper_stuck,1800,100"
python -m ppcl rules                        # every rule and what it checks
python -m ppcl help                         # the built-in documentation

--help works on the top level and on every subcommand.

Changing the port. The workbench serves on 8765 unless told otherwise, and there are three ways to tell it, in order of precedence:

  • ppcl.bat 8800 or python -m ppcl serve --port 8800 -- for that launch only
  • Settings -> Workbench -> Server port -- saved with the workspace, and used every time after, including by a double-clicked ppcl.bat
  • otherwise 8765

If the port is already taken the workbench says so and stops, rather than quietly starting somewhere else -- usually it means one is already running.

If your programs only ever reach a panel from a workstation and are never typed at a panel's serial port, add --workstation-only to lint. It drops the line-length findings, which are usually most of the output on anything written in Desigo.

To install it properly instead, so that ppcl is on the path:

pip install -e .

Then ppcl lint ... works from anywhere. The install pulls in nothing; the dependency list is empty and meant to stay that way.


The app

python -m ppcl.cli serve --workspace .

Opens a local IDE in the browser with six panes over everything below.

Editor

A PPCL editor that checks as you type. Open reads a program from anywhere on the machine — a Desigo or Insight .pcl export, say — or drop the file on the window. Multi-file tabs, syntax coloring, and error, warning and unresolved-point markers in the gutter — click a finding to jump to it.

Everything the Desigo CC PPCL Editor does to a program, this does to a file, with the same keys so muscle memory transfers: Ctrl+G go to statement, Ctrl+F find and replace, Ctrl+/ comment, Ctrl+wheel to zoom, quick numbering on Enter, and Command Assist using Siemens' own eight command categories, with the signature and the argument you are on shown as you type.

It adds what Desigo has nowhere to put: 90 lint rules, each citing the manual page it comes from, and a set of source transforms that are exact by machine and tedious by hand — DEFINE expand and collapse, point-name separator swap, clone a block of statements with renames and retargeted branches, and enable/disable statements.

Builder

Author from a decision table — equipment down the side, modes across the top. This is Siemens' own recommended planning method, not an invention here. Modes, interlocks, control loops, reset schedules and free-form rules each get a form; the document text and the generated PPCL stay in step with the forms either way you edit.

The compiler guarantees by construction what you would otherwise check by eye: exactly one backward GOTO and it is last, every interlock force matched by a RELEAS at the same priority, and no time-based command inside an IF or a subroutine.

Blocks

Draw the control as blocks and wires — 30 block types across inputs, logic, maths, control, timing and outputs — and compile that to PPCL as you draw.

The compiler is the interesting part. Pure logic and arithmetic stay as expressions, so an AND of two comparisons is one statement rather than three statements and two locals. A value condenses into a named local only when it feeds more than one block, holds state, is timed, would exceed the 16-operand statement limit, or you gave the block a name — which is how a wire on the drawing gets a name you can look up at the panel.

A loop of pure logic is refused, naming the blocks in it. A loop through a latch or a delay is allowed, reads the previous pass's value, and says so in the generated program.

Bench

Run the program against simulated equipment: mixing box, coils, fan, zone with thermal mass, sensor lag, actuator stroke time, damper leakage. Pick the weather, inject a fault, read the trends. Point priority arbitration is exact, so a command refused because the point is owned at a higher priority is reported — which is the defect this catches most often.

Bench → Debug

A real debugger over the same interpreter:

  • Line breakpoints, for "why does this branch never run".
  • Write watchpoints, which stop on the statement that wrote a point and name the line — for "something is commanding this and I cannot find what".
  • Conditional breakpoints, written as PPCL expressions and evaluated against live point values.

Step, step over, step out, run to cursor, a watch window showing each point's value and its current priority, coverage marking for lines that have never run, and the one thing you cannot do on a panel: override any point mid-run and carry on.

Settings and Help

Firmware, editor behavior, bench defaults, theme, and the point database import. Settings are stored as JSON in the workspace and validated on load — a bad value is reported with its limit rather than quietly clamped.

The Help pane carries the full documentation, including what is verified against the manual and what is approximated.

Point database

Import a CSV or JSON export from Desigo CC or Insight. Columns are matched by name, and anything unrecognised is reported rather than guessed at. Loading one turns on three things: unresolved-reference marking in the gutter (the same red U the Desigo editor shows, produced offline), type-aware lint rules, and real point names in Command Assist.


Safety

Zero dependencies here too: the server is http.server, and the UI is plain ES modules with no framework and no build step.

Nothing here touches a building system. No panel writes, no network client, no BACnet or P2 connection. The workbench reads and writes files; you load the result through Insight or Desigo CC yourself.

The server binds 127.0.0.1 and confines all file access to the workspace directory. Paths that escape it are refused rather than normalized; so are hidden files and folders (.git, .claude), drive-relative paths, files with no extension, and any extension outside the PPCL set. Binding elsewhere with --host prints a warning, because the API has no authentication and can write files. On Windows it refuses to start if the port is already taken, rather than silently sharing it with another instance.

Simulation is a model. The equipment models are first-order lumped approximations, good for exercising control logic and worthless as a load calculation. The LOOP output value is approximated — Siemens does not publish the PID form — and says so at runtime. Never take a tuning constant from the bench to a real panel. Long bench runs lower the simulated line rate to stay responsive, and the response says when it did.

No statement's behavior has been validated against a live panel. Every command signature traces to the manual or to Desigo CC's own Command Assist, which is a stronger claim than "tested" and close to the whole claim being made.

The grammar is a step further along. An independent project reading APOGEE P2 traffic ran this parser over 2,644 lines recovered from programs running on panels and it handled all of them; Siemens' own 115 worked examples take command coverage to 57 of 66. Nothing there says a modeled behavior is right — only that the language is read correctly.


Why

PPCL has no compiler, no type checker, and no way to try a change except on a live panel. The language actively invites a handful of failures that are invisible on the screen and expensive in the building:

Failure What you see on the panel Rule
Point latched at @EMER, never released Schedule silently stops working W330
LOOP/TOD/WAIT outside the main loop Runs once at load, then never again E205
Duplicate line number One line silently vanishes on load E102
SAMPLE/TIMAVG inside a GOSUB Timing drifts unpredictably E213
GOSUB inside IF/THEN Undefined per the manual E214
Two unconditional writers on one point Behavior depends on line order W332

Every rule cites the section of the APOGEE PPCL User's Manual (125-1896) it comes from, so a finding can be argued with a vendor rather than just asserted.


Commands

lint — check programs

python -m ppcl.cli lint programs/ --min-severity warning
python -m ppcl.cli lint AHU1.ppcl --points panel.csv --format json
python -m ppcl.cli lint programs/ --firmware logical --disable W104 --strict
  • --points takes a point database (name,type CSV or JSON) which turns on type-aware checks such as analog equality comparison.
  • --firmware selects apogee (default), logical, physical, unitary, cm. Several rules differ by firmware — SET accepts integers on APOGEE only.
  • --strict exits non-zero on warnings, for CI.

90 rules across five groups: E1xx syntax, E2xx/W2xx control flow, E3xx/W3xx semantics and priority, S6xx style, P7xx optimization. python -m ppcl.cli rules lists them all.

run — simulate a program offline

python -m ppcl.cli run AHU1.ppcl --set MAT=35 --set OAT=20 --time 8.0 \
    --passes 20 --interval 30 --trace writes

Executes the program against made-up sensor values on a virtual clock and shows what it does, including priority arbitration — the thing you cannot see by reading. Blocked commands are called out explicitly:

3 command(s) were blocked by point priority:
  line 120: ON SFAN blocked: point is at @EMER, command is at @NONE

--scenario file.json loads starting values and a clock. --format json gives the full event trace for scripting.

Fidelity is stated honestly. Assignment, arithmetic, IF/THEN/ELSE, GOTO/GOSUB/RETURN, all the commanding verbs and their priority rules, MAX, MIN, TABLE, DBSWIT, TIMAVG, SAMPLE, WAIT, TOD, TODSET, TODMOD, HOLIDA and the enable/disable family are exact. LOOP is an approximation — Siemens does not publish the internal PID form — and says so at runtime. PDL, SSTO, OIP and DC/DCR are traced as no-ops.

seq — author without writing PPCL

python -m ppcl.cli seq new -o AHU1.seq          # starter document
python -m ppcl.cli seq check AHU1.seq           # validate, then lint the result
python -m ppcl.cli seq compile AHU1.seq -o AHU1.ppcl
python -m ppcl.cli seq bench AHU1.seq --weather design_winter
python -m ppcl.cli seq json AHU1.seq            # the same document as JSON

You describe the sequence; the compiler writes the PPCL. The primary surface is a decision table of equipment against modes, which is Siemens' own recommended design artifact (Desigo CC, "PPCL Program Plans"):

sequence "AHU-1 single zone"
  equipment AHU1

points
  SFAN    LDO
  HVLV    LAO
  MAT     LAI
  DMD     local

modes
  Unoccupied  otherwise
  Occupied    when TIME between 6:00 and 18:00

table
              Unoccupied  Occupied
  SFAN        off         on
  OADPR       closed      20
  HVLV        closed      modulate

interlock Freeze
  trip when MAT < 38
  reset when MAT > 45
  force SFAN off at emer

loop Discharge
  measure DAT
  output DMD
  setpoint DASP
  acting reverse
  throttling 10
  range 0 to 100

Each point carries its panel type (LDO, LAI, MV...), local for a program local, or - to take it from the loaded point database.

Modes are listed lowest priority first and the last match wins, so putting a shutdown mode after the occupied mode is all it takes to override it. A cell saying modulate emits nothing and leaves the point to its loop; anything else overrides the loop, because the table is compiled after it.

A safety can drive a whole column. Interlock latches are computed before modes, so a mode can be written when Freeze is on and the table then shows, in one place, what every piece of equipment does during that shutdown:

modes
  Unoccupied  otherwise
  Occupied    when TIME between 6:00 and 18:00
  Shutdown    when Freeze is on

table
              Unoccupied  Occupied  Shutdown
  SFAN        off         on        off
  HVLV        closed      modulate  closed
  CVLV        closed      modulate  closed

This is worth preferring over forcing points one at a time. An interlock that only drops the fan leaves the discharge loop running against no airflow, where it saturates and drives the heating and cooling valves at once -- a defect the bench caught in this project's own example sequence.

What the compiler makes impossible, rather than merely detectable:

  • Exactly one backward GOTO, and it is the last statement — the only one the Desigo compiler permits.
  • Every interlock gets its matching RELEAS at the same priority. The most common PPCL field defect cannot be written.
  • No time-based command inside an IF or a subroutine, so LOOP, TABLE and SAMPLE are evaluated every pass as the manual requires.
  • Line references stay symbolic until render, so nothing points at a stale line.

The text form, the JSON, and the compiled PPCL are three views of one document, and text→JSON→text round-trips exactly. Compilation is deliberately one way: a document compiles to PPCL reliably, but arbitrary hand-written PPCL does not lift back into a table, because real GOTO structure carries intent a table cannot represent.

new — generate a program

python -m ppcl.cli new ahu --author "A Tech" --organization ACME -o AHU1.ppcl
python -m ppcl.cli new schedule --points-list "SFAN,RFAN,EFAN"
python -m ppcl.cli new leadlag --points-list "CHWP1,CHWP2"
python -m ppcl.cli new reset --option inp=OAT --option out=HWSP
python -m ppcl.cli new skeleton --title "AHU-3 rebuild"

Templates: skeleton, ahu, reset, schedule, leadlag. Every generated program is linted before it is handed back, and all of them lint clean — the ahu template deliberately includes the matched RELEAS that the freeze-latch bug is missing.

For programmatic authoring, ppcl.generator.Builder lets you write against symbolic labels instead of raw line numbers:

from ppcl.generator import Builder

b = Builder()
b.label("MAIN")
b.code("IF(TIME.GE.6:00) THEN ON(SFAN) ELSE OFF(SFAN)")
b.goto("MAIN")          # resolved to a real line number at render time
print(b.render())

Engineering helpers compute the values the manual gives formulas for: proportional_gain(device_range, throttling_range), integral_gain(pg), loop_bias(lo, hi), duty_cycle_pattern(slots), table_statement(...).

Writing files. fmt, renumber, transform, blocks and seq fmt write a file back the way it was read: the same encoding (a Windows-1252 degree sign stays B0), byte-order mark and line endings. With -i they keep a byte-exact .bak unless told --no-backup, and write through a temporary file so a failure leaves the original whole. A line with no line number -- an export header, stray text -- would be lost by a rewrite, so the file is refused until it is fixed or --force is given. A folder only expands to .ppcl and .pcl files for these commands; a .txt has to be named outright.

renumber — renumber safely

python -m ppcl.cli renumber AHU1.ppcl --preserve-blocks -i

Rewrites every GOTO, GOSUB, ACT, DEACT, ENABLE, DISABL and ONPWRT reference to match, including references nested inside IF/THEN/ELSE and behind a SAMPLE. --preserve-blocks keeps the thousands-block layout used for subroutines.

On duplicate line numbers it refuses by default. The panel keeps only one copy but the file holds both, so renumbering has to either drop code or change what the panel runs. Pick explicitly:

  • --split-duplicates — every line survives, each gets its own number. This makes the program do more than the one in the field.
  • --allow-duplicates — keep the first of each, matching the panel today.

bench — run against simulated equipment

python -m ppcl.cli bench AHU1.ppcl --weather design_winter --seconds 10800
python -m ppcl.cli bench AHU1.ppcl --fault "AHU1,oa_damper_stuck,1800,100"
python -m ppcl.cli bench AHU1.ppcl --format csv --chart AHU1.actual_dat > run.csv
python -m ppcl.cli bench --list-faults

Runs the program against a simulated air handler -- mixing box, hot and chilled water coils, fan, zone thermal mass, and sensors with realistic lag -- on a virtual clock. The program only ever sees the sensors, which is the point: a sequence tuned against instantaneous perfect measurements is a sequence that hunts in the field.

--fault injects a failure at a given second and asks whether the sequence catches it: oa_damper_stuck, hw_valve_leak, supply_fan_proof_fail, mat_sensor_fail, coil_fouling, hot_water_loss and others.

Checks make a run pass or fail instead of producing numbers to squint at -- freeze stat never trips, coil face stays above 36 F, fan does not short cycle, zone held between 66 and 78 F. A scenario file (--scenario) defines the plant, bindings, faults and checks together.

Model fidelity is stated, not implied. These are first-order lumped models in IP units, good for exercising control logic. They are not a load calculation and not an energy model. LOOP output values are approximate and say so at runtime.

graph, points, explain

python -m ppcl.cli graph AHU1.ppcl              # loop entry, subroutines, branches
python -m ppcl.cli graph AHU1.ppcl --format dot | dot -Tpng -o flow.png
python -m ppcl.cli points programs/             # cross-program point inventory
python -m ppcl.cli explain LOOP                 # command, with the manual's notes
python -m ppcl.cli explain EMER                 # the priority hierarchy
python -m ppcl.cli explain E205                 # what a rule means and why

blocks — compile a block diagram

python -m ppcl.cli blocks diagrams/ahu1-freeze.blocks.json
python -m ppcl.cli blocks diagrams/ahu1-freeze.blocks.json --in-place

Compiles the JSON a Blocks-pane drawing saves to, lints the result, and writes the PPCL -- with --in-place, beside the diagram as ahu1-freeze.ppcl. Exits non-zero if the program has errors, so it works in CI.

transform — the edits that are exact by machine

python -m ppcl.cli transform expand-defines AHU1.ppcl
python -m ppcl.cli transform underscores AHU1.ppcl --in-place
python -m ppcl.cli transform clone AHU1.ppcl --first 200 --last 340     --rename AHU1.SFAN=AHU2.SFAN --rename AHU1.MAT=AHU2.MAT

expand-defines / collapse-defines, dots / underscores for point-name separators, disable / enable / comment on selected lines, and clone to copy a block of statements with points renamed and branches retargeted. All of them work on a real parse, so a decimal point or a .AND. is never mistaken for a name separator. Each reports exactly what it changed.

db — point database and unresolved references

python -m ppcl.cli db exports/points.csv
python -m ppcl.cli db exports/points.csv --check programs/

Imports a CSV or JSON export and lists every point a program names that the database does not contain — the offline equivalent of the red U the Desigo PPCL Editor shows in its status column. Exits non-zero when there are any.

help — the built-in documentation

python -m ppcl.cli help                 # the contents
python -m ppcl.cli help priority        # one page
python -m ppcl.cli help --search releas

The same pages the Help pane shows, in the terminal.

redact — share a program safely

python -m ppcl.cli redact programs/ --outdir /tmp/shareable --mapping local-map.json

Replaces site-identifying names while leaving the control logic byte-identical, so a program can go to a vendor or into a ticket without carrying the building's topology. Generic HVAC vocabulary (SFAN, OAT, AHU01) is preserved so the code stays readable; --aggressive replaces that too. Comment bodies are dropped entirely rather than rewritten — free text is where tenant names and room numbers actually live, and no token substitution catches that reliably.

The mapping file is the only thing that reverses it. Keep it local.


Library

from ppcl import parser, linter, analyzer

prog = parser.parse_file("AHU1.ppcl")
a = analyzer.analyze(prog)

a.steady_state      # lines that execute every pass
a.one_shot          # lines that run once at startup and never again
a.subroutines       # GOSUB entry -> body, RETURNs, callers
a.loop_entry        # first line of the main loop

for d in linter.lint(prog):
    print(d.code, d.severity.value, d.line, d.message)

Modules: spec (the language, machine-readable), lexer, parser, ast_nodes, analyzer (control and data flow), linter + rules/, formatter (format and renumber), unparse, simulator, debug (breakpoints, stepping, watch), generator, transforms (source edits), points (the panel database), settings, helpdocs, sequence/ (document model, text form, compiler), blocks/ (block catalog and the diagram compiler), plant/ (equipment models and the test bench), web/ (JSON API and the UI), redact, cli.


Tests

python -m pytest tests -q

434 tests. The rule tests each include a case that must fire and, where a false positive is plausible, a case that must stay quiet. The sequence and block compilers are checked with property tests -- every compiled program is asserted to have one backward GOTO and for it to be last, to keep every time-based command out of an IF, to declare every local it uses, and to lint without errors -- so the guarantees survive a change to the generated layout.


Sources

Everything in ppcl/spec.py traces to the APOGEE Powers Process Control Language (PPCL) User's Manual, 125-1896, Rev. 5 (10/00), Siemens Building Technologies — its 11 point types (Table 3-2), the priority hierarchy (Table 3-1), the operator precedence table (Table 2-6), the reserved word list (Chapter 5), and every command signature (Chapter 4).

The Desigo CC engineering help supplies what the 2000 manual predates: the compiler's own error list, the operand and operator limits, Cross Trunk point referencing, the subroutine benefit table, and the Command Assist categories this workbench reuses verbatim so its command list filters the way the Desigo editor's does.

See docs/PPCL-REFERENCE.md for the condensed language reference, the failure catalog, and the places where the sources contradict each other -- including ATN versus ARC, where the same Desigo page spells the arc-tangent both ways.

Other PPCL tooling

For syntax highlighting alone there are editor modes for Vim, Notepad++ and Kate, and a Sublime Text package that adds renumbering with GOTO rewriting and DEFINE toggling. Example programs live in delphian/ppcl-library, four of which are the regression fixtures in samples/.

There is no other linter, simulator, debugger or block editor for this language that I could find.

License

MIT. See LICENSE.

About

PPCL Workbench: IDE, linter, simulator and debugger for Siemens PPCL (APOGEE/PXC). 90 lint rules, each cited to the manual. Python stdlib, runs locally.

jamesccupps.github.io/PPCL/

Topics

apogeebasbuilding-automationclaude-codecontrolsdesigodomain-specific-languagehvacidelintermcp-serverparserppclpxcpythonsequence-of-operationssiemenssimulatorstatic-analysiszero-dependency

Resources

Readme
MIT license

Security policy

Security policy
Activity

Stars

3 stars

Watchers

1 watching

Forks

0 forks
Report repository

Releases

Packages

Used by

Contributors

Languages

You are visitor 01402775 — GeezerVison does not store the pages you look up.
Best viewed with Netscape Navigator 4.7 or Internet Explorer 6 at 800×600. No cookies required.