A python library for design of earthing networks in electrical substations.
- Earth grid design as per IEEE 80 / ENA EREC S34.
- Electrode resistance by IEEE formulae where available, with ENA EREC S34 and IS 3043 alternatives:
- grid (IEEE 80 Eq. 52) and grid with rods (Schwarz, IEEE 80 Eqs. 53-56; or ENA S34 R4-R6);
- rod (IEEE 80 / ENA S34 R1), strip and plate (Dwight, IEEE 142; or ENA S34 R7, R2).
- Mesh and step voltage for rectangular, L-shaped and irregular grids (IEEE 80), with perimeter or interior rods.
- Permissible touch and step voltage: IEEE 80 (50 kg and 70 kg) and ENA TS 41-24 Tables 1 and 2.
- Surface, touch and step potential formulae of ENA EREC S34 (P1-P7).
- Electrode current density limits: ENA S34 C2 (default), IS 3043 and IEEE 142.
- Numerical earth network calculations using boundary discretisation method, validated against the EPRI results of IEEE 80 Annex B Examples 1-4.
- 3D plotting of electrode geometry used for design.
- 3D plotting of current density distribution for the earth network.
- 2D/3D plotting of surface potential distribution.
- Plotting and evaluation of mesh and step potentials.
- User guide: installation, units, workflows, and examples.
- API reference: exported functions, parameters, return values, and
Networkmethods. - Validation: checks against IEEE Std 80-2000, ENA EREC S34, ENA TS 41-24, IS 3043:2018 and IEEE Std 142 worked examples and tables, with the latest report.
Package is available on PyPI for installation (https://pypi.org/project/earthing). Use python3 -m pip install earthing to install.
Program source includes detailed usage instructions for various functions and classes. Alternately project page has ipython notebooks covering typical use cases.
from earthing import resistance_grid_with_rods, e_mesh_step_grid, e_touch_70 # 70 m x 70 m grid, 11 x 11 conductors (d = 10 mm) at 0.5 m, 20 rods x 7.5 m R = resistance_grid_with_rods(400, 4900, 1540, 7.5, 20, 14, 0.016, None, b=0.01) Em, Es = e_mesh_step_grid(400, 70, 70, 7.5, 11, 11, 20, 0.01, 0.5, 1908) print(R, Em, Es, e_touch_70(400, 2500, 0.102, 0.5))
Recent versions changed some default formulae. Pass method= to keep the earlier behaviour:
| Function | New default | Earlier formula |
|---|---|---|
resistance_grid_with_rods |
'IEEE80' (Schwarz) |
method='S34' |
resistance_plate |
'IEEE142' (Dwight) |
method='S34' |
resistance_strip |
'IEEE142' (Dwight) |
IS 3043:1987 (removed); method='S34' for ENA S34 R7 / IS 3043:2018 |
max_current_density |
'S34' (Formula C2) |
method='IS3043' |
Descrete* classes and descretise() are renamed Discrete* and discretise(); the old names still work with a DeprecationWarning.
validation/ checks the package against worked examples and tables of IEEE Std 80-2000, ENA EREC S34, ENA TS 41-24, IS 3043:2018 and IEEE Std 142 (231 cases). Run:
python3 validation/run_validation.py
See validation/README.md for coverage, tolerances, solver step-size guidance and the issues found in the standards.
- Python 3
- Numpy
- Matplotlib